Tel:400 008 9119 Login  CN | EN

JBF-61S30-H

Electrical Fire Monitoring Equipment


JBF-61S30-H electrical fire monitoring equipment connects to detectors and sensors in the field to discover electrical abnormality in early stage and prevent electrical fire from happening.
The field devices mainly include the residual current type electrical fire detectors which monitor current leakage of protected circuit, and the temperature monitoring type electrical fire detectors which monitor ambient environment.
The design, production and inspection of this product comply with GB 14287.1-2014 “Electrical fire monitoring system – part 1: electrical fire monitoring equipment”.
 
Product Features

•  Two-wire data transmission. No power cable is needed for field devices. This makes wiring easy.
•  High resolution 7-inch color LCD screen, information-rich, beautiful display; the user interface introduces GUI design, friendly person-machine interaction.
•  Multilevel password management enables different levels of operational permission.
•  The equipment provides accurate date and time record for events to seconds with Real-time clock.
•  Up to 100000 pieces of historical record.
•  The equipment supports data upload and download via PC/USB and other ways.
•  The loop protocol supports "conflict avoidance" and "preemption".
•  The equipment can network with JB Fire control panel. Up to 99 control panels/equipments can connect to the network.
•  The equipment can discover ID-duplicated filed devices via Online-inspection, and can reset their addresses.
•  Long distance communication - the maximum transmission distance for field devices is 1500 meters.
•  Can print out monitor equipment status information in real time with built-in Mini printer. Users can choose information categories to print what they need.

Technical Parameters
NAME PARAMETERS
Product nameElectrical fire monitoring equipment
ModelJBF-61S30-H
Standard compliedGB 14287.1-2014: Electrical fire monitoring system – part 1: electrical fire monitoring equipment
Capacity4 loops, 1008 addresses
NetworkSupports network of up to 99 control panels/equipment
Aux outputBuilt-in 2 sets of dry-contact output on the loop board; can program as fault output or alarm output.
Rated Power InputMain power: AC220V  
frequency: 50±1HZ
Rated Power OutputSystem power supply: 24V/2A,
auxiliary power supply: 24V/3A
Power consumption20W
Batteries12V/7AH ×2
Working environmentTemperature: -10℃~+50℃
Relative humidity: ≤93%
Sound pressure≥70DB
Dimensions440MM×125MM×540MM (LXWXH)
Protection gradeIP30
 