CAUTION
(1)To avoid electrocution that could result in personal injury or death, remove all sources of power and allow 10 minutes to discharge stored energy prior to installing or removing equipment. Install this device in accordance with all applicable codes and the Local Authorities Having Jurisdiction.
(2) Electrical supervision requires breaking the wire run at each terminal. Do not loop the signaling circuit field wires around the terminals.
(3)Check the manufacturer’s installation instructions for other equipment used in the system for any guidelines or restrictions on wiring and/or locating NACs and notification appliances. Some system communication circuits and/or audio circuits, for example, may require special precautions to assure electrical noise immunity (e.g., audio crosstalk).
(4)Check that the installed product will have sufficient clearance and wiring room prior to installing bases. Do not over tighten mounting screws as this can deform the base and may affect operation.
INSTALLATION
1.Mount the FW900 base onto a 4x4 electrical box, see Figure 2.
Figure 2. Base Installation2.Set the strobe signal level to the desired setting. See Figure 3.
Figure 3. Candela Selector3.Connect the wires. See Figure 4 and Figure 5.
(a) Class A Circuit without Audible Silence Feature (b) Class A with Audible Silence Feature
(c) Class B without Audible Silence Feature (d) Class B with Audible Silence Feature Figure 4. Wiring Diagram with FW951 Sync Module
(a) Class A Circuit (b) Class B Circuit Figure 5. Wiring Diagram with FW106/FW106C FACP
4.Combine the (horn) strobe with base – Align the (horn) strobe onto the base then and twist it in clockwise.
5.Test for proper operation. Initiate this unit from the connected FACP and observe for proper operation.
MAINTENANCE
Scheduled inspection and operational test should be carried as per requirement set out by Local Authority Having Jurisdiction.
Return the device for reparation if it fails to alarm during testing. Do not disassemble the detector without permission.