JBF4372E2

Sounder Beacon
The sounder beacon is composed of DC24V, fire alarm circuit, LED light circuit and corresponding processing circuit. When fire occurs, the control panel gives out fire command. Then the sounder beacon gives alarm sound and LED flashes.

Product Features
  Built-in microprocessor.
  Adopt SMT process.
  Four cables, two of bus lines (non-polar) and two of power supply that are 24V and GND (non-polar).
  There is no special requirement for the cable used during construction, as long as the conductor cross-section area is not less than 1.0mm2.
 
Technical Features

ItemParameters
Working voltageDC 24V
Alarm current≤50mA (24V)
Alarm volume80.0dB~100.0dB24V, A weighting
Modulation cycle2.0S~4.0S
Flash rate1.5Hz~2.0Hz
Addressing methodElectrical encoding
Address range1-200
Operating temperature-10—+55℃
Relative Humidity≤93%RH (40±2℃)
Weight108g
Dimensionsφ100mm、H66.9mm
Applied placesIndoors, non-residential area
WiringSignal lines L1 and L2 (non-polar);24V power line V, G(non-polar)
Applied standardGB 26851-2011 “Audible and/or visual fire alarm signaling appliances”
 
Structure and Dimensions



Wiring
1) After wiring construction, fix the base on the wall with 60mm mounting hole spacing.
2) Before installation, write address (1-200) to the device using encoder.
3) The loop is connected to terminal L1, L2 on the base; DC24V and GND are connected to the base V and G.
4) The sounder beacon should be installed after wiring inspection and before debugging to prevent losses caused by improper installation
 
Precautions

Conduct alarm test regularly, recommended every six months.