JBE-2101



Applied to EN standard, connecting to the input or the loop. When front panel of the MCP is pressed down, MCP sends alarm signal to the control panel.
JBE-2101
Overview
JBE-2101 is a conventional manual call point (MCP) designed to be compatible with a wide range of conventional fire panels and input modules. This MCP sets an installer-selectable resistive load to the fire loop when its resettable element is pressed.
After activation, the MCP will remain in alarm until it is reset with the supplied reset key. There is no glass break element in this device, so the reset operation is conveniently done without the need to replace any element.
The JBE-2101 also features a pair of normally open clean (voltage-free) contacts, which close at activation. These can be optionally used for a local action or to provide an activation signal to third party systems.


Technical data
CategoryEN 54-11 type A indoor MCP
Working voltageDC 6-30 V
Connection2-wire conventional zone
Wire size0.5 – 2.5 mm2
Quiescent current0 mA
AlarmloadBuilt-in 680 Ω and 470 Ω + option for external R.
Clean contact rating0.1A/30V DC
Working temp-10℃~55℃
Storage temp-30℃~75℃
Environment Humidity≤95%RH (no condensation nor icing)
Red LED IndicationSteady on when in alarm
Dimensions (LxWxH)90×90×52mm
IP ratingIP40
Weight0.16kg
StandardEn 54-11
Declaration of Perf.DoP-0370-CPR-3804-1
 
Installation
Always observe local fire and electric installation regulations.
1.Secure the base to the wall (surface or flush mounted).
2.Identify the system's requirement for MCP alarm level (typically 680 Ω or 470 Ω). For other alarm loads, an external resistor may be used in conjunction with the internal dry contact. Note that the LED will not be powered from the 
dry contact terminals.
3.Connect the conventional zone wiring to the MCP base.
•  For 470 Ω zones, connect the wires as per diagram A
•  For 680 Ω zones, connect the wires as per diagram B

4.Insert the MCP face into its base and push firmly, the MCP can be secured to the base by fitting an optional self-tapping screw (ST2.9x8) into its boss next to the reset keyhole.
6.Test each MCP and wiring integrity after installation.

Resetting an activated Manual Call Point                  
1.Open the tab in the bottom of the MCP face.
2.Insert the reset key.
3.Rotate key counterclockwise until the frangible element returns to its position.


Mechanical dimensions

Mechanical dimensions (all dimensions in mm) and connection diagram
 
TerminalsConnection
1 & 2Conventional zone (-) for 470 Ω zone
3 &4Conventional zone (-) for 680 Ω zone
5 & 6[Optional] Dry contact  (0.1A 30V DC)
7 & 8Conventional zone (+) for all configurations