JBE-2101
Applied to EN standard, connecting to the input or the loop. When front panel of the MCP is pressed down, MCP sends alarm signal to the control panel.
Category | EN 54-11 type A indoor MCP |
Working voltage | DC 6-30 V |
Connection | 2-wire conventional zone |
Wire size | 0.5 – 2.5 mm2 |
Quiescent current | 0 mA |
Alarmload | Built-in 680 Ω and 470 Ω + option for external R. |
Clean contact rating | 0.1A/30V DC |
Working temp | -10℃~55℃ |
Storage temp | -30℃~75℃ |
Environment Humidity | ≤95%RH (no condensation nor icing) |
Red LED Indication | Steady on when in alarm |
Dimensions (LxWxH) | 90×90×52mm |
IP rating | IP40 |
Weight | 0.16kg |
Standard | En 54-11 |
Declaration of Perf. | DoP-0370-CPR-3804-1 |
Terminals | Connection |
1 & 2 | Conventional zone (-) for 470 Ω zone |
3 &4 | Conventional zone (-) for 680 Ω zone |
5 & 6 | [Optional] Dry contact (0.1A 30V DC) |
7 & 8 | Conventional zone (+) for all configurations |