Tel:400 008 9119 Login  CN | EN

JBF5174

JBF5174 Sounder Beacon Manual

Overview


JBF5174 sounder beacons is used in Jade Bird Fire JBF-11SF and JBF5000 series fire alarm systems. The sounder beacon gives high decibel alarm sounds and flashes LED light when a fire occurs in public place. Suitable for indoor (non-residential) public places, such as hotel rooms, office buildings, libraries, theaters, postal buildings, etc.

  Product features

 

 Applied scope

 

  Model name composition



Techinical Data

Environment features
Working temperature-10~+55℃
Storage temperature-20~+65℃
Relative humidity≤95% (no condensation)
 
Electrical features
Working voltageDC18V-28V, modulation type, provided by control panel
Monitoring current≤ 190uA
Alarm current≤ 6mA (DC24V)
SPL80.0dB~115.0dB  (DC24V,  A-Weighted)
Frequency cycle4.0s~5.0s
Flashing rate1.0Hz~1.5Hz
 
Communication
WiringTwo-wire, no polarity
Address range1~200
Addressing methodElectronic encoder
Max communication distance1000m
 
 
Compatibility
Connect to JBF-11SF and JBF5000 series control panel.
 
Mechanical features
AppearancePANTONE T085-2-1
MaterialPC (Cover) + ABS (base)
Weight150g
DimensionsΦ100mm×H52mm (with base)
IP gradeIP34
 
Applied standard
1GB 26851-2011 “Audible and/or visual fire alarm signaling appliances”
 
 

Installation

 Installation steps