| Number of detection loops | 1 or 2 |
| User-selectable detection loop topologies | Class A (ring) or Class B (stub) |
| 24 V outputs to field devices | 2 |
| Maximum number of detection zones | 400 |
| Maximum number of output groups | 400 |
| Maximum loop distance | 2000 m |
| Recommended cable type | 2 x 1.5 mm² unshielded twisted pair |
| Maximum number of addressable points (Free mix of detectors, MCP, IO, sounders) | 200 per Class A loop (max 2 x 200) |
| Detection loop voltage | JBE pulsed protocol (20 to 30 Vpp) |
| Detection loop available current | 2 x 200 mA |
| DC outputs to field devices | 2 x 2 A @ 24 V DC |
| Field cable access to panel cabinet | Ø20 mm knockouts (14x) |
| Connection type | Normally-Open voltage-free relay |
| Electrical contact ratings | 2A @ 30 VDC |
| Mains voltage | AC 230 V (196 – 253 V) |
| Mains fuse | 2.5 A slow acting |
| Power rating (mains) | 2.5 A max |
| Max. sustained DC output current (Imax a) | 4 A |
| Max. alarm DC output current (Imax b) | 5.5 A |
| Operating temperature | -5 to +40 °C |
| Storage temperature | -20 to +55 °C |
| Environment humidity (non-condensing) | < 95 % (no condensation nor icing) |
| Ingress Protection category | IP30 |
| Dimensions (WxHxD) | 440 mm x 370 mm x 126 mm |
| Weight (without batteries) | 4 kg |
| Weight (including 12 Ah batteries) | 12 kg |
| Standards | EN 54-2 EN 54-4 |
| Declaration of Performance | DoP-0370-CPR-3813-1 |