Number of detection loops | 1 or 2 |
User-selectable detection loop topologies | Class A (ring) or Class B (stub) |
24 V outputs to field devices | 2 |
Maximum number of detection zones | 400 |
Maximum number of output groups | 400 |
Maximum loop distance | 2000 m |
Recommended cable type | 2 x 1.5 mm² unshielded twisted pair |
Maximum number of addressable points (Free mix of detectors, MCP, IO, sounders) | 200 per Class A loop (max 2 x 200) |
Detection loop voltage | JBE pulsed protocol (20 to 30 Vpp) |
Detection loop available current | 2 x 200 mA |
DC outputs to field devices | 2 x 2 A @ 24 V DC |
Field cable access to panel cabinet | Ø20 mm knockouts (14x) |
Connection type | Normally-Open voltage-free relay |
Electrical contact ratings | 2A @ 30 VDC |
Mains voltage | AC 230 V (196 – 253 V) |
Mains fuse | 2.5 A slow acting |
Power rating (mains) | 2.5 A max |
Max. sustained DC output current (Imax a) | 4 A |
Max. alarm DC output current (Imax b) | 5.5 A |
Operating temperature | -5 to +40 °C |
Storage temperature | -20 to +55 °C |
Environment humidity (non-condensing) | < 95 % (no condensation nor icing) |
Ingress Protection category | IP30 |
Dimensions (WxHxD) | 440 mm x 370 mm x 126 mm |
Weight (without batteries) | 4 kg |
Weight (including 12 Ah batteries) | 12 kg |
Standards | EN 54-2 EN 54-4 |
Declaration of Performance | DoP-0370-CPR-3813-1 |