FW962R



UL listed, connect to NAC, polar two-wire, LED light source of low power consumption and high luminous intensity, sound signal and light signal can achieve system level synchronization after startup, conventional type.
FW962R
DESCRIPTION
The FW962R/W Horn Strobes and FW982R/W Strobes are a family of multi-candela visual and audible signal appliances with light sources generated from white LED, listed according to UL 1971, UL 1638, UL 464, ULC-S525 and ULC-S526 for indoor use. The LED light source offers superior performance, including low power consumption and long operating life. Six levels of light output are selectable. Figure 1 shows relative light outputs in horizontal and vertical dispersion from strobes mounted on walls/ceilings.
The strobe appliances produce a flash rate of one flash per second over the Regulated Voltage Range. The temporal tone generated by the horn portion is designed as per ANSI and NFPA72 for standard emergency evacuation signaling requirement.
The appliance has the feature that can synchronize multiple horn and/or strobes in a complete fire alarm system.

---- UL Limit (percent)
---- FW962R/FW962W/FW982R/FW982W intensity (percent)
Figure 1. Horizontal and Vertical Light Outputs
ATTENTION
The product must be used within its published specifications and properly installed, operated, and maintained, in accordance with these instructions. Users are solely responsible for determining whether a product is suitable for the user’s purposes or achieves the intended results. Read the instructions carefully before using this product. Failure to comply with any of the instructions, cautions, and warnings could result in improper application, installation and/or operation of these products in an emergency situation. This could result in property damage and serious personal injury or death.
 
NOTE
Do not paint this device.
Any material extrapolated from this document or from Maple Armor’s instructions or other documents describing the product for use in promotional or advertising claims, or for any other use, including description of the product’s application, operation, installation, and testing is the sole responsibility of the user. Maple Armor will not assume any liability for such use. In no case will Maple Armor’s liability exceed the purchase price paid for a product.
 
SPECIFICATION
Operating Voltage           16 to 33 VDC/FWR
RMS Operating Current @16 Vdc(mA) 130cd105cd85
cd
50
cd
35
cd
20
cd
FW962R
FW962W
16412685554730
FW982R
FW982W
15611980494328
RMS Operating Current @16Vfwr (mA) 130cd105cd85
cd
50
cd
35
cd
20
cd
FW962R
FW962W
187158102665838
FW982R
FW982W
15415097615335
Sound Level
(dBA)
Voltage16V dc/fwr24V dc/fwr33V dc/fwr
UL
Reverberant
778185
ULC
 Anechoic
858891
Directional CharacteristicsHorizontal
Axis
AngleOSPL (dBA)
0° (ref)0 (ref)
± 44°-3
± 54°-6
± 90°-10.5
Vertical
Axis
AngleOSPL (dBA)
0° (ref)0 (ref)
± 52°-3
± 55°-6
± 90°-12
Effective Light (cd)130, 105, 85, 50, 35, 20
(See Figure 3 for candela selection)
Operating Temperature0° C to 49° C (32° F to 120° F)
Operating Humidity 0 to 93% RH
Horn PatternTemporal 3
Strobe Pattern1 flash per second
Wire Size 12 to 18 AWG
Location Indoor wall/ceiling
Compatible ModelFW951 Sync Module, FW106 / FW106C FACP
 
CAUTION
(1)To avoid electrocution that could result in personal injury or death, remove all sources of power and allow 10 minutes to discharge stored energy prior to installing or removing equipment. Install this device in accordance with all applicable codes and the Local Authorities Having Jurisdiction.
(2) Electrical supervision requires breaking the wire run at each terminal. Do not loop the signaling circuit field wires around the terminals.
(3)Check the manufacturer’s installation instructions for other equipment used in the system for any guidelines or restrictions on wiring and/or locating NACs and notification appliances. Some system communication circuits and/or audio circuits, for example, may require special precautions to assure electrical noise immunity (e.g., audio crosstalk).
(4)Check that the installed product will have sufficient clearance and wiring room prior to installing bases. Do not over tighten mounting screws as this can deform the base and may affect operation.
 
INSTALLATION
1.Mount the FW900 base onto a 4x4 electrical box, see Figure 2.

Figure 2. Base Installation

 
2.Set the strobe signal level to the desired setting. See Figure 3. 


Figure 3. Candela Selector

 
3.Connect the wires. See Figure 4 and Figure 5.
                     
                              (a) Class A Circuit without Audible Silence Feature             (b) Class A with Audible Silence Feature
                  
                              (c) Class B without Audible Silence Feature                        (d) Class B with Audible Silence Feature
Figure 4. Wiring Diagram with FW951 Sync Module

                            
(a) Class A Circuit                                                             (b) Class B Circuit
Figure 5. Wiring Diagram with FW106/FW106C FACP

 
4.Combine the (horn) strobe with base – Align the (horn) strobe onto the base then and twist it in clockwise.
5.Test for proper operation. Initiate this unit from the connected FACP and observe for proper operation.
 
MAINTENANCE
Scheduled inspection and operational test should be carried as per requirement set out by Local Authority Having Jurisdiction.
Return the device for reparation if it fails to alarm during testing. Do not disassemble the detector without permission.