Tel:400 008 9119 Login  CN | EN

JTW-LD-JBF4310

JTW-LD-JBF4310
Overview
JTW-LD-JBF4310 temperature sensing cable has the ability to continuously monitor the temperature of the protected object of its full length. It has the functions of fixed temperature alarm, rate-of-rise alarm, and adjustable multi-level sensitivity, which can quickly report the fire situation. It has excellent anti-interference ability and can effectively avoid false alarm. Main application scope: cable trench, tunnel, interlayer, substation and other places.
 
Product Features
Long detection range of temperature sensing cable: 10-1000m.
Detector type: recoverable, fixed temperature and rate-of-rise heat detector, its standard alarm length is 1m.
Alarm threshold setting: fixed temperature alarm threshold 85 ℃, 60℃-85 ℃ settable.
View temperature in the field: the display interface can check and display the temperature of the detection point of the temperature sensing cable.
Regional alarm temperature setting: alarm threshold can be set separately in different zones, range 60-85 ℃.
Technical Data

ItemsTechnical Parameters
Working environment
Working temperature-10~+55℃;
Storage temperature-20~+65℃
Relative humidity≤95%
Electrical features
Working voltageDC20V~DC28V
Monitoring current<200mA (DC24V)
Alarm current<350mA (DC24V)
IndicatorAlarm (red), fault (yellow), operation (green)
Detector typeRecoverable, fixed temperature and rate-of-rise heat detector, its standard alarm length is 1m.
Alarm threshold settingsFixed temperature and rate-of-rise heat detector, its standard alarm length is 1m.
Temperature viewingDisplay temperature of each detection point.
Region alarm threshold settingsAlarm threshold can be set separately in different zones, range 60-85 ℃.
 
Communication
Output relayRS485 (MODBUS protocol) CAN communication, voltage-free signal output, LA loop.
Compatibility
11sf and jbf5000 series control panel
Mechanical features
Protection rateIP67
Dimensions (detector)175mm×127mm×74mm (L×W×H) installation bracket not included.
Detection
Alarm threshold60~+85℃
Detection range10-1000m
Certification
Fire certification, explosion-proof certification
Applied standard
Gb 16280 -2014
 
Technical Data Comparison

FeaturesOrdinary linear temperature sensitive cableJade Bird Fire linear temperature sensitive cable
Detection range200m1000m
alarm threshold85℃ and 105℃,alarm threshold can be set from 60 °C  to 85°C
Rate-of-rise alarm thresholdFixed properties (thermosensitive materials)Adjustable rate-of-rise alarm sensitivity
Temperature displayNADisplay temperature of each detection point.
Region alarm threshold settingsNAAlarm threshold can be set separately in different zones.
 
Dimensions and installation



For the fire detection in the cable area, the temperature sensing cable should be laid with sine wave contact.


Notes: for other applications, please follow the relevant design specifications or contact the manufacturer.
Wiring


Terminals of signal processing unit
Attention
The sensing cable is different from ordinary cables. Excessive extrusion will cause mechanical damage inside the cables and cause false alarms. Therefore, the following principles should be followed in the installation process:
1) When laying the sensing cable, the pull tension shall not be greater than 100N, and the bending radius shall be greater than 30cm.
2) Avoid heavy objects sitting on the cable. The sensing cable should be installed in places free of mechanical damage.
3) Pay attention to the polarity of the cable connection. Reverse connection will cause cable damage.
4) When there are joints in the sensing cables, the junction box must be added. The wiring must follow the requirements, and the sealing of the junction box must ensure the stable operation of the sensing cable.
5) Do not open the cover with power connected. Non-professional personnel are not allowed to install or dismantle the product.
6) After connecting the cable, restore the sealing ring to the original position and tighten the box cover.