Two-wire, non-polar, no need for DC24V power cord, using common model base, easy to install and fully compatible with all models of Jade Bird Fire control panels.
Items | Technical Parameters |
Working voltage | DC18V-27Vmodulation type provided by the control panel |
Wiring | Signal line: L1, L2 Polarity-free |
Working temperature | -10~+50℃ |
Storage temperature | -20~+55℃ |
Relative humidity | ≤95%(40±2℃) |
Monitoring current | ≤0.25mA(24V) |
Alarm current | ≤1mA(24V) |
Output capacity | DC30V /2A |
RF susceptibility (immunity) | 30V/M |
Indicator | Input indicator and output indicator flash when in normal monitoring; input indicator steady on when input is activated; output indicator steady on when output is activated; input indicator off when input has fault; output indicator off when output has fault. |
Dimensions | 85mm×85mm×41mm |
Addressing method | Electrical encoder |
Address range | 1-200 |
Communication distance | 1500m |
Applied standard | GB 16806-2006 “Automatic Control System for Fire Protection” |