JBF5175 Sounder Beacon
Manual
(Please read carefully before use)
Overview
BF5175 sounder beacons is used in Jade Bird Fire JBF-11SF and JBF5000 series fire alarm systems. The sounder beacon gives high decibel alarm sounds and flashes LED light when a fire occurs in public place, and hash Chinese and English voice reporting function. Suitable for indoor (non-residential) public places, such as hotel rooms, office buildings, libraries, theaters, postal buildings, etc.
Product features
- Built-in crested ibis microprocessor that specialized in fire protection.
- Adopt SMT process.
- Two-wire, polarity free loop.
- It is recommended to use twisted cable for the loop. Its cross-sectional area should not be less than 1.5 mm2.
- Support three kinds of alarm sounds, can alarm in turns with Chinese and English voice reporting, and can set sound-only alarm and light-only alarm.
Applied scope
- The sounder beacon connect to JBF-11SF and JBF5000 series control panel.
- Applicable to indoor (non-residential) public places, such as hotel rooms, office buildings, libraries, theaters, post office buildings.
- The application applies to GB 50116-2013 “Code for fire protection design of buildings”
Model name composition
Techinical Data
Environment features
Working temperature | -10~+55℃ |
Storage temperature | -20~+65℃ |
Relative humidity | ≤95% (no condensation) |
Explosion-proof
Electrical features
Loop voltage | DC18V-28V, modulation type, provided by control panel |
Rated voltage | DC 24V |
Monitoring current | Loop: ≤ 1.5mA DC 24V: ≤ 40mA |
Alarm current | Loop: ≤ 3mA DC 24V: ≤ 125mA |
SPL | 70.0dB~115.0dB (DC24V, A-Weighted) |
Frequency cycle | 4.0s~5.0s |
Flashing rate | 1.0Hz~1.5Hz |
Communication
Wiring | Four-wire, no polarity |
Address range | 1~200 |
Addressing method | Electronic encoder |
Max communication distance | 1000m |
Compatibility
Connect to JBF-11SF and JBF5000 series control panel. |
Mechanical features
Appearance | PANTONE T085-2-1 |
Material | PC (Cover) + ABS (base) |
Weight | 166g |
Dimensions | Φ100mm×H52mm (with base) |
Applied standard
1 | GB 26851-2011 “Audible and/or visual fire alarm signaling appliances” |
Installation
Installation steps
- The sounder beacon adopts unfolded installation.
- After the wiring, fix the base of the sounder beacon to the wall (using M4 bolts), pitch of holes: 45mm~68mm.
Figure 1 Appearance and dimensions
- Before installation, use an electronic encoder to write the corresponding address to the product. The address should be consistent with the one in the engineering software.
- Connect the two wires of the loop to terminals 1 and 2, polarity-free.
- Connect DC24V to terminals 3 and 4, polarity-free.
- The sounder beacon should be installed after wiring inspection and before debugging to prevent losses caused by improper installation
The sounder beacon wiring diagram (see figure 2)
Commissioning
- First use electronic encoder to write address to the sounder beacon. The address range is 1 ~ 200.
- After successfully writing the address, connect the sounder beacon to the control panel to register it.
- In case of fire, the control panel sends out fire command, and the sounder beacon gives out sound alarm, voice reporting and LED flashing light alarms.
- Set working mode of the sounder beacon through special address:
Working mode | Special address | Notes |
Alarming type | 201 | |
Sound only | 202 | |
Light only | 203 | |
- Set alarm sound of the sounder beacon through special address:
Sound alarm | Special address | Notes |
Alarm sound and Chinese/English voice reporting | 204 | |
beep and Chinese/English voice reporting | 205 | |
honk and Chinese/English voice reporting | 209 | |
- Set status of the sounder beacon through special address:
Status | Special address | Notes |
Addressable | 206 | |
Reset to factory status | 208 | Sound alarm, alarming type, addressable |
Troubleshooting
Trouble | Causes | Solutions | Notes |
The control panel reports fault | Loop not connected. | Rewire the loop. | |
The actual address of the sounder beacon is not the same as the one in engineering software. | Write address to the product following the project engineering software. | |
Unable to register the device | The device is not addressed. | Address the device using encoder. | |
Loop is not correctly connected | Check the wiring. | |
Address number is out of range | Address range: 1-200 | |
Maintenance
- Daily maintenance, maintenance, and calibration
- Conduct alarm test regularly, every six months recommended.
Out-of-box check
Open the package and check the follow parts are included:
sounder beacon | 125/package, base not included |
Manual | 10/package |
After opening the package, please check the appearance and functions of the product. Should there be any loss or damage to the sounder beacon, please contact us soon. Once determined that the damage is not caused by human factors, we will replace it for the customer immediately.
Disclaimer
- The Company reserves the right to finally interpret this manual.
- The steps in this manual must be strictly followed for installation and commissioning.