JBF6145-D

Four-wire, applicable to normally open double door that are normally with power. When activated, the power is cutoff and it close the electric door closer and electromagnetic discharger.
Input/Output Module
The function of JBF6145-D is similar to that of JBF6141-D, except that this product is designed especially for the double fire door. It has two sets of output that controlling two door closers and occupies only one address on the loop.

Product Features
•  Embedded micro-processer.
•  Supplied by 24V power supply; gives out 24V relay output.
•  Two-wire polarity-free loop, low power consumption.
•  A communication distance of 1500m.
•  Twisted pair cable is recommended in the installation. The cross-section of the cable should not be less than 1.5mm².
•  Electrical isolation between signal processing circuit and input/output checking circuit,reliable performance.
•  Plug in structure, easy to install and maintain.
•  With state monitoring and fault detection functions.

Technical Data
ItemsTechnical Parameters
Power inputDC 16-30V
LoopTwo-wire, polarity-free, modulation type;
Working current≤0.1mA
Relay outputDC24V/1A
Addressing methodElectrical encoder
Address range1-252
IndicatorMonitoring: “operation” and “output” red indicator flashe.
Activation and feedback: “operation” red indicator brightly flashes, and “output” red indicator is steady on;
Fault: “operation” red indicator flashes twice in a row.
Dimensions120mm ×82mm ×43mm(L×W×H)
 
Structure and Dimensions
 
Wiring

•  L1 (terminal 1, 2) and L2 (terminal 3, 4): polarity-free, connect to the loop.
•  24V (terminal 8) and GND (terminal 6): connect to 24V DC power. Pay attention to the polarity.
•  Input function: AS (terminal 15) and GND (terminal 16): connect to the feedback terminals (volt-free).
•  Output function: CO1(terminal 12),CO2(terminal 10),GND(terminal 11, terminal 13) connect to the equipment to be controlled. After activation, CO1(terminal 12)and CO2(terminal 12) give 24V output.
•  Factory default settings: after activation, CO1 is first activated, and CO2 is activated after 6 seconds. The duration of 6 seconds can be changed using encoder, range: 1-30 seconds. 
Notes:

•  The feedback terminals of the connecting equipment that connect to AS and GND should add a 10KΩ EOLR in parallel.
•  A 10KΩ EOLR must be connected in parallel between CO1 and GND, also between CO2 and GND.
•  A diode should be connected between CO1 and GND, also between CO2 and GND, and pay attention to the direction of the diode.